NA2XY (Al/XLPE/PVC)

Power cable : Indoors, cable trunking, outdoors 
and burried in the ground, for power stations, 
industry and switchgear as well as for urban 
supply networks, if mechanical damage is 
unlikely.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape

10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
10 - 800 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

  • Specification
  • Download File

Spesifikasi Produk NA2XY (Al/XLPE/PVC)

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx. approx.
mm² mm kg/km
10 8.5 84
16 9.7 113
25 11.3 156
35 12.5 196
50 14.1 257
70 16.2 335
95 18.1 425
120 19.6 500
150 22.5 639
185 25.0 783
240 28.0 1,008
300 30.5 1,208
400 36.0 1,696
500 39.0 1,982
630 43.5 2,473
800 48.0 3,037

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area DC Resistance at 20°C AC Resistance at 90°C Trefoilformation Flat formation    
in air in ground in air in ground
(mm²) Max. (Ω/km) Max. (Ω/km) (mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.336 0.382 60 71 62 70 0.94
16 1.91 2.449 0.311 0.357 81 92 84 91 1.50
25 1.20 1.539 0.302 0.348 109 118 112 117 2.35
35 0.868 1.113 0.289 0.335 134 142 138 140 3.29
50 0.641 0.822 0.279 0.325 165 168 170 166 4.70
70 0.443 0.568 0.269 0.316 211 206 218 203 6.58
95 0.320 0.411 0.263 0.309 260 245 269 242 8.93
120 0.253 0.325 0.260 0.306 303 279 312 275 11.28
150 0.206 0.265 0.258 0.304 353 313 364 309 14.10
185 0.164 0.212 0.258 0.304 411 355 424 350 17.39
240 0.125 0.162 0.253 0.299 494 412 510 406 22.56
300 0.100 0.130 0.249 0.295 571 465 590 458 28.20
400 0.0778 0.103 0.245 0.292 688 536 711 528 37.60
500 0.0605 0.081 0.245 0.291 796 609 823 599 47.00
630 0.0469 0.065 0.243 0.289 932 692 963 680 59.22
800 0.0367 0.053 0.241 0.287 1074 778 1111 764 75.20

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information