NAYY (Al/PVC/PVC)

Power cable : Indoors, cable trunking, outdoors 
and burried in the ground, for power stations, 
industry and switchgear as well as for urban 
supply networks, if mechanical damage is unlikely.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated

Note :
Conductor Shape

10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
10 - 800 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%

  • Specification
  • Download File

Spesifikasi Produk NAYY (Al/PVC/PVC)

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx. approx.
mm² mm kg/km
10 9.1 103
16 10.3 135
25 11.9 186
35 13.1 231
50 15.0 306
70 17.1 391
95 19.2 498
120 21.0 583
150 23.5 725
185 26.0 886
240 29.0 1,142
300 32.0 1,388
400 37.5 1,904
500 40.5 2,219
630 44.5 2,709
800 48.5 3,272

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area DC Resistance at 20°C AC Resistance at 70°C Trefoilformation Flat formation    
in air in ground in air in ground
(mm²) Max. (Ω/km) Max. (Ω/km) (mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
10 3.08 3.701 0.350 0.396 49 59 50 58 0.76
16 1.91 2.295 0.323 0.370 66 77 68 76 1.22
25 1.20 1.442 0.313 0.359 88 98 91 97 1.90
35 0.868 1.043 0.298 0.344 109 118 112 117 2.66
50 0.641 0.770 0.290 0.336 134 233 138 138 3.80
70 0.443 0.533 0.279 0.325 170 140 175 169 5.32
95 0.320 0.385 0.274 0.320 210 171 216 202 7.22
120 0.253 0.305 0.270 0.316 244 205 251 229 9.12
150 0.206 0.249 0.265 0.312 283 261 291 258 11.40
185 0.164 0.198 0.264 0.310 328 296 339 292 14.06
240 0.125 0.152 0.260 0.306 395 344 407 339 18.24
300 0.100 0.122 0.258 0.304 456 388 471 382 22.80
400 0.0778 0.096 0.252 0.298 548 447 565 440 27.20
500 0.0605 0.076 0.251 0.298 633 507 653 499 34.00
630 0.0469 0.061 0.246 0.293 738 576 762 566 42.84
800 0.0367 0.050 0.242 0.289 848 646 877 635 54.40

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information

Daftar File NAYY (Al/PVC/PVC)